The research into the heating effect of secondary steel structures, having no fire proofing, on the fire resistance of fireproof steel beams

https://doi.org/10.22227/0869-7493.2021.30.03.16-30

Abstract

Introduction. The international practice of passive fire protection design, as well as some manufactures of fireproofing products recommend to apply fire proofing substances not only to the main element, whose fire resistance limit is standardized, but also to the elements that do not fall under any fire resistance standards. Various support brackets, pipeline supports (hereinafter — PS), etc. can serve as examples. They are not considered as bearing elements according to SP (Construction Regulations) 2.13130.2020, although they are connected to the structures that have fireproofing applied. It is recommended to apply fireproofing substances to such PS within the range of, at least, 450 mm from the point of attachment to the fireproof structure when the area of the PS cross section exceeds 3,000 mm2. No “supplementary” fireproofing is required by the Russian design and fire protection regulations.
The subject of research. A change in the fire resistance limit of steel i-girders, caused by the PS heating, depends on the area of the PS cross section and the location of the point of its attachment.
The goal. The goal of the research is to analyze the effect, produced by the area of the cross section and the point of attachment, on the fire resistance limit of fireproof steel i-girders in the course of heating.
Materials and methods. ANSYS Workbench 2020 R2 (student version) was applied to perform the numerical simulation.
Results. The simulation has shown that the PS, having no fireproofing, influences the fire resistance limit of fireproof structures.
Conclusions. Currently available methods of analysis of the fire resistance of steel structures take no account of the fire resistance limit reduction, caused by the heating of the PS that has no fireproofing. The numerical simulation has shown that the fire proofing design must take account of the potential reduction in the fire resistance limit of fireproof structures, exposed to the heated PS that has no fire proofing. The further verification of the effect, produced by the PS, that has no fireproofing, on the time to the limit state of a fireproof steel i-girder requires fire tests and supplementary investigations to evaluate the influence of the PS on the heating of vertical fireproof constructions, including the case of the hydrocarbon fire mode.

About the Authors

A. O. Vorosin
Branch of Linde GmbH; Moscow State University of Civil Engineering (National Research University)
Russian Federation

Anatoliy O. Vorosin, Chief Engineer, Magistrate

Galaktionovskaya St., 102, Samara, 443001

Yaroslavskoye Shosse, 26, Moscow, 129337



A. P. Parfenenko
Moscow State University of Civil Engineering (National Research University)
Russian Federation

Aleksander P. Parfenenko, Cand. Sci. (Eng.), Associate Professor of Department of Integrated Safety in Civil Engineering, Deputy Head of Institute of Integrated Safety in Construction

Yaroslavskoye Shosse, 26, Moscow, 129337

ID RISC: 800496

Scopus Author ID: 57214086032

ResearcherID: AAP-2933-2020



References

1. Guidance on passive fire protection for process and storage plant and equipment. Energy Institute, 2017; 115.

2. Yakovlev A.I. The calculation of fire resistance of steel structures. Moscow, Stroyizdat Publ., 1988; 144. (rus).

3. Roytman V.M. The engineering solutions for fire resistance evaluation of designed and reconstructed buildings. Association “Fire safety and science”, 2001; 382. (rus).

4. Roytman V.M. Fire resistance of building material as a basic characteristic of fire resistance kinetic theory. Pozhary i chrezvychaynye situatsii: predotvrashchenie, likvidatsiya/Fires and emergencies: prevention, elimination, 2019; 1:62-69. (rus).

5. Roytman V.M., Serkov B.B., Pristupnyk D.N. A way forward of fire resistance theory development of structures, buildings and frame structures considering combining special loads together with fire. XXIX International Scientific-Practical Conference, dedicated to 80th anniversary of FGBU VNIIPO of EMERCOM of Russia : in 2 parts. Part 2: Combustion and problems of extinguishing fires : abstracts. Report. Moscow, VNIIPO, 2017; 42-45. URL: https://elibrary.ru/item.asp?id=29942736 (rus).

6. Roytman V.M., Golovanov V.I. Need for technical regulation of the buildings fire resistance taking into account the possible combined hazardous fire exposure. Pozharnaya bezopasnost’/Fire safety. 2014; 1:86-93. (rus).

7. Golovanov V.I., Pavlov V.V., Pekhotikov A.V. Assessment of quality application of fire protection means on steel constructions of buildings and structures of various functional purposes. Pozharnaya bezopasnost’/Fire safety. 2015; 3:74-82. (rus).

8. Shebeko Yu.N., Shebeko A.Yu., Zuban A.V. Determination of required thicknesses of an intumescent fire redundant coating on steel structures for given fire resistance limits. Pozharnaya bezopasnost’/ Fire Safety. 2020; 1:26-29. (rus).

9. Shebeko Yu.N., Zuban A.V., Shebeko A.Yu. An evaluation of an actual fire resistance limit of non-protected steel structures for different temperature regimes of fires. Pozharovzryvobezopasnost/ Fire and Explosion Safety. 2019; 28(6):29-34. DOI:10.18322/PVB.2019.28.06.29-34 (rus).

10. Perelmuter A.V. Fire design of steel structures. International Journal for Computational Civil and Structural Engineering. 2019; 15(1):110-118. DOI: 10.22337/2587-9618-2019-15-1-110-118 URL: https://ijccse.iasv.ru/index.php/ijccse/article/view/195

11. Molchadskiy I.S. The fire in a room. Moscow, VNIIPO, 2005; 456. (rus).

12. Amdahl J., Holmas T., Skallerud B. Ultimate strength of structural members with attachments during accidental fires. International Conference Response of Structures to Extreme Loading. Toronto, Canada, 2003.

13. Friebe M., Jang B.S., Jim Y. A parametric study on the use of passive fire protection in FPSO topside module. International Journal of Naval Architecture and Ocean Engineering. 2014; 6:826-839. DOI: 10.2478/IJNAOE-2013-0216

14. Podolski D., Wang Y.-C., Yuan J. Numerical investigation of intumescent ‘coatback’ on unprotected secondary beams. Applications of Fire Engineering –– Proceedings of the International Conference of Applications of Structural Fire Engineering, ASFE. 2017; 161-170.

15. Necip Onder Akinci, Krishna Parvathaneni, Abhimanyu Kumar, Hyun-Su Kim, Michael Stahl, Xiaowei Dai. Advanced fire integrity analysis and PFP optimization methods for petrochemical facilities. 21st Annual international Symposium October, Texas. 2018.

16. Munoz-Garcia E. Analysis and design challenges and solutions of 3 sided passive fire protection PFP on steel beam desks for offshore installations. Offshore Technology Conference Asia. 2016. DOI: 10.4043/26623-MS

17. Imran M., Liew M.S., Nasif M.S., Munoz Garcia E., Danyaro K.U., Niazi M.U. Thermal and mechanical response of partially protected steel I-beams under fire. MATEC Web of Conference. 2018; 203:06009. DOI: 10.1051/matecconf/201820306009

18. Botyan S.S., Zhamoydik S.M., Kudryashov V.A., Olesiyuk N.M. Heating of rod steel structures with partial and full fire-protected external surface under fire exposure. Journal of Civil Protection. 2020; 4(1):20-31.

19. Pekhotikov A.V. The fire resistance of bended steel structures : dissertation for Ph.D. in Engineering Science. Moscow, 2008. 198 p. (rus).

20. Golovanov V.I. The Forecasting of steel structures fire resistance : dissertation for Advanced Doctor in Engineering Science. Moscow, 2008; 337. (rus).

21. Wang W., Zhang L. An approach for evaluating fire resistance of steel beams considering creep effect. Procedia Engineering. 2017; 210:544-550. DOI: 10.1016/j.proeng.2017.11.112

22. Ishimov A.S., Baryshnikov M.P., Chukin M.V. On the selection of a mathematical function of the equation of state for a description of rheological properties of steel 20 during hot plastic deformation. Vestnik of G.I. Nosov Magnitogorsk State Technical University. 2015; 1:43-52. URL: https://elibrary.ru/item.asp?id=23166465 (rus).

23.


Review

For citations:


Vorosin A.O., Parfenenko A.P. The research into the heating effect of secondary steel structures, having no fire proofing, on the fire resistance of fireproof steel beams. Pozharovzryvobezopasnost/Fire and Explosion Safety. 2021;30(3):16-30. (In Russ.) https://doi.org/10.22227/0869-7493.2021.30.03.16-30

Views: 552


Creative Commons License
This work is licensed under a Creative Commons Attribution 4.0 License.


ISSN 0869-7493 (Print)
ISSN 2587-6201 (Online)