Investigation of fire resistance of steel structures covering a warehouse building under different temperature conditions
https://doi.org/10.22227/PVB.2020.29.03.54-65
Abstract
Aims and purposes. The purpose of the study is to assess the convergence of the “standard” temperature regime and possible “real” temperature regimes of fires in modern warehouse buildings, as well as the correspondence of actual fire resistance limits to the effects of “real” fires. To achieve this goal, the following tasks were solved: mathematical modeling of the development of a “real” fire by the field method in a warehouse building at different fire loads was carried out, as well as modeling of heating of the supporting structures of the coating according to the standard temperature regime and the “real” temperature conditions of the fire obtained during the simulation; the required fire resistance limits of the bearing building structures of the coating are determined through the equivalent duration of the fire.
Methods. A storage building of a standard form with dimensions of 12×12×6.5 m was chosen as the object of the study. The building has a 4×4 meter gate in the amount of 2 pieces and an entrance door of 1×2 meter size. Within the walls of the building are 32 windows measuring 0.7×1 meter. Coverage — an impassable flat roof over metal trusses. The parameters of the fire load during mathematical modeling were taken according to the reference data of Yu.A. Koshmarov 12 types of typical fire load stored in warehouse buildings are considered. For mathematical modeling of “real” temperature fires, the “Fire Dynamics Simulator” (FDS) software package was used, which implements a field (differential) mathematical model. For mathematical modeling of the heating process of steel building structures, the finite-difference method for solving the Fourier heat equation with external and internal nonlinearity was used, implemented in the ANSYS Mechanical software package. results and discussion. The results of modeling in the FDS software package show that the temperature impact on the structure according to the standard temperature regime for fire loads: cables+wires, industrial oil, ethyl alcohol was less, which indicates an underestimation of the thermal impact on the structure. The results of modeling the heating of structures showed that the heating time of the coating truss is up to 400–700 °C for fire loads: cables+wires, industrial oil, ethyl alcohol less than the time obtained from standard tests, which indicates an initial underestimation of the actual fire resistance of steel structures of the coating when designing warehouse buildings.
Conclusions. The assumption that the thermal impact of the standard temperature regime on the steel structures of modern warehouse complexes was underestimated was confirmed for 3 of the 12 fire loads considered, namely: cables+wires, industrial oil, ethyl alcohol.
About the Author
D. A. MinailovRussian Federation
Denis A. MINAILOV, Deputy Chief, Forensic Institutions Federal Fire Service “Fire testing laboratory”. ResearcherID: AAI-2064-2020; Scopus Author ID: 57207307581
236010, Kaliningrad, Basseynaya St., 35 a
References
1. Yakubson V.M. Prospects of metal as a construction material. Magazine of Civil Engineering. 2015; 2(54):4-5. DOI: 10.5862/MCE.54.1 (rus.).
2. Yakovlev A.I. Calculation of fire resistance of building structures. Moscow, Stroyizdat, 1988; 143. (rus.).
3. Roitman V.M. Engineering decision of fire resistance projected and reconstructed buildings. Moscow, Pozhnauka, 2001; 382. (rus.).
4. Eremina T.Y., Minaylov D.A. Harmonization of the Russian and international normative documents on assessment of fire resistance of structures (key approaches to carrying out fire tests). Fire Safety. 2014; 2:151-155. (rus.).
5. Roitman V.M. Consideration of real fire condition while calculating the fire resistance of building structures on the basis of the kinetic approach. Fire Safety Journal. 1990; 16:433-442.
6. Phan L.T., McAllister T.P., Gross J.L., Hurley M.J. Best Practice Guidelines for Structural Fire Resistance Design of Concrete and Steel Buildings. NIST Technical Note 1681. Gaithersburg, Maryland, NIST, 2010; 200. DOI: 10.6028/nist.tn.1681
7. Garlock M., Kruppa J., Li G.-Q., Zhao B. White Paper on Fire Behavior of Steel Structures. NIST GCR 15-984. Gaithersburg, Maryland, NIST, 2014; 20. DOI: 10.6028/nist.gcr.15-984
8. Kotsovinos P. Analysis of the structural response of tall buildings under multifloor and travelling fires. Edinburgh, The University of Edinburgh, 2013; 240.
9. Kowalski R. The use of Eurocode model of reinforcing steel behavior at high temperature for calculation of bars elongation in RC elements subjected to fire. Procedia Engineering. 2017; 193:27-34. DOI: 10.1016/j.proeng.2017.06.182
10. Razdolsky L. Structural Fire Loads: Theory and Principles. New York, McGraw-Hill Education, 2012; 448.
11. Du Y. A new temperature-time curve for fire-resistance analysis of structures. Fire Safety Journal. 2012; 54:113-120. DOI: 10.1016/j.firesaf.2012.07.004
12. Mouritz A.P., Feih S., Kandare E., Gibson A.G. Thermal–mechanical modelling of laminates with fire protection coating. Composites Part B: Engineering. 2013; 48:68-78. DOI: 10.1016/j.compositesb.2012.12.001
13. Outinen J., Samec J., Sokol Z. Research on fire protection methods and a case study “Futurum”. Procedia Engineering. 2012; 40:339-344. DOI: 10.1016/j.proeng.2012.07.105
14. Gogoberidze N.V., Blagorodova N.V. On the automation system for determining the fire resistance of building structures. Engineering Journal of Don. 2012; 4-1(22):110. (rus.).
15. Puzach S.V. Mathematical modeling of gas dynamics and heat and mass transfer in solving fire and explosion safety problems. Moscow, Academy of State Fire Service of EMERCOM of Russia, 2002; 149. (rus.).
16. Koshmarov Y.A. Predicting indoor fire hazards: a training manual. Moscow, Academy of State Fire Service of EMERCOM of Russia, 2000; 118. (rus.).
17. Abashkin A.A., Karpov A.V., Ushakov D.V., Fomin M.V., Giletich A.N., Komkov P.M., Samoshin D.A. Manual on the application of “Methods for determining the calculated values of fire risk in buildings, structures and structures of various classes of functional fire hazard”. Moscow, VNIIPO, 2014; 226. (rus.).
18. Golovanov V.I., Pavlov V.V., Pekhotikov A.V. Engineering method of design of fire resistance of steel constructions protected by “ROCKWOOL CONLIT” mineral wool boards. Fire Safety. 2006; 4:78-85. (rus.).
19. Korolchenko D., Eremina T., Minailov D. New method for quality control of fire protective coatings. IOP Conference Series: Materials Science and Engineering. 2019; 471(11). DOI: 10.1088/1757-899X/471/11/112016
20. Lucherini A., Giuliani L., Jomaas G. Experimental study of the performance of intumescent coatings exposed to standard and non-standard fire conditions. Fire Safety Journal. 2018; 95:42-50. DOI: 10.1016/j.firesaf.2017.10.004
Review
For citations:
Minailov D.A. Investigation of fire resistance of steel structures covering a warehouse building under different temperature conditions. Pozharovzryvobezopasnost/Fire and Explosion Safety. 2020;29(3):54-65. (In Russ.) https://doi.org/10.22227/PVB.2020.29.03.54-65