The analysis of the fire resistance limit of an enclosing wall with a wave-resisting visor as the protection for a group of fuel oil tanks
https://doi.org/10.22227/0869-7493.2021.30.06.73-86
Abstract
Introduction. An enclosing wall with a wave-resisting visor may be installed to resist the flow of a liquid spill during a tank collapse in accordance with GOST R 53324-2009. This wall should be continuous along the perimeter; it must be made of incombustible materials and have the fire-resistance limit of not less than E 150. As a rule, varieties of heavy concretes are used to construct these walls. However, the actual fire-resistance limit of a structure depends on both its geometric parameters, thermal characteristics and strength properties of concrete used in the case of the long-term exposure to the hydrocarbon fire regime. The work addresses the assessment of the actual fire resistance limit of an enclosing wall with a wave-resisting visor made of heavy concrete designed as the protection for a group of tanks at fuel oil facilities of a thermal power plant.
Calculation methodology and results. The calculation of the actual fire resistance limit of an enclosing wall with a wave-resisting visor, designated for a group of fuel oil tanks was performed. The co-authors used the results of studies on the substantiation of a hydrocarbon fire resulting from a flammable liquid spill and a tank failure, empirical dependences for determining the thermal engineering parameters of heavy concrete, as well as experimental data on a change in the compressive strength of concrete at temperatures up to 1,200 °C. The calculation results show that this wall structure can maintain stability for more than 10 hours. Note that the load-bearing capacity of the wall is more than 11 times greater than the bending moment triggered by the standard load. Indeed, the fire resistance of the wall is not less than RE 600. It exceeds the normative values for these types of walls by a factor of four.
Conclusions. A common algorithm can be used to calculate the actual fire-resistance limit of enclosing walls of oil and petroleum product tank storage facilities, set by Construction Regulations 468.1325800.2019. At the same time, the results of the above theoretical and experimental studies are recommended for use as the initial data.
About the Authors
S. A. ShvyrkovRussian Federation
Sergey A. Shvyrkov, Dr. Sci. (Eng.), Professor, Professor of Department of Fire Safety of Technological Processes as part of the Educational and Scientific Complex of Fire Safety of Protection Objects
ID RISC: 479363
Borisa Galushkina St., 4, Moscow, 129366
Ya. I. Yuryev
Russian Federation
Yan I. Yuryev, Cand. Sci. (Eng.), Senior Lecturer of Department of Fire Safety of Technological Processes as part of the Educational and Scientific Complex of Fire Safety of Protection Objects
ID RISC: 765228
Borisa Galushkina St., 4, Moscow, 129366
A. P. Petrov
Russian Federation
Anatoliy P. Petrov, Dr. Sei. (Eng.), Professor, Professor of the Department of Fire Safety of Technological Processes as part of the Educational and Scientific Complex of Fire Safety of Protection Objects
ID RISC: 765316
Borisa Galushkina St., 4, Moscow, 129366
V. P. Nazarov
Russian Federation
Vladimir P. Nazarov, Dr. Sei. (Eng.), Professor, Professor of the Department of Fire Safety of Technological Processes as part of the Educational and Scientific Complex of Fire Safety of Protection Objects
ID RISC: 764644
Borisa Galushkina St., 4, Moscow, 129366
References
1. Nazarov V.P., Brushlinskij N.N., Shvyrkov S.A., Goryachev S.A., Suchkov V.P., Chirko A.S. Ensuring of fire safety of urban construction objects under the development of transport infrastructure in the domain of permissible risk. Environmental protection in the oil and gas complex. 2009; 1:20-31. (rus).
2. Zaripova A.R., Ganieva A.A., Kolesnik A.A. Analysis of prognostic problems of petroleum spreads in tank parks. Petroleum Engineering. 2017; 15(2):192-196. (rus).
3. Vladimirov V.A. Oil spills: causes, magnitude, consequences. Civil Protection Strategy: Problems and Research. 2014; 4(1):217-229. URL: https://www.elibrary.ru/item.asp?id=21490-612 (rus).
4. Shvyrkov S.A. Fire risk in case of quasi-instantaneous destruction of an oil tank : monograph. Moscow, Academy of the state fire Service of emercom of Russia Publ., 20 15; 289. (rus).
5. Zaytsev A.M., Tul’skaya S.G., Sklyarov K.A. Causes and consequences of the accident at the fuel and lubricants warehouse at CHPP 3 of the city of Norilsk. Urban planning. Infrastructure. Communications. 2021; 3(24):38-42. (rus).
6. Yur’yev Ya.I. Fire and industrial safety (construction industry). Moscow, 2018; 152. (rus).
7. Stucchi R., Amberg F.A. A practical approach for tunnel fire verification. Structural Engineering International. 2020; 30(4):515-529. DOI: 10.1080/10168664.2020.1772697
8. Yan Zhi-guo, Shen Yi, Zhu He-hua, Li Xiao-jun, Lu Yong. Experimental investigation of reinforced concrete and hybrid fibre reinforced concrete shield tunnel segments subjected to elevated temperature. Fire Safety Journal. 2015; 71:86-99. DOI: 10.1016/j.firesaf.2014.11.009
9. Yi Na-Hyun, Choi Seung-Jai, Lee Sang-Won, Kim Jang-Ho Jay. Failure behavior of unbonded bi-directional prestressed concrete panels under RABT fire loading. Fire Safety Journal. 2015; 71:123-133. DOI: 10.1016/j.firesaf.2014.11.010
10. Ingason Haukur, Zhen Li Ying, Lönnermark A. Runehamar tunnel fire tests. Fire Safety Journal. 2015; 71:134-149. DOI: 10.1016/j.firesaf.2014.11.015
11. Khan A.A., Usmani A., Torero J.L. Evolution of fire models for estimating structural fire-resistance. Fire Safety Journal. 2021; 124:103367. DOI: 10.1016/j.firesaf.2021.103367
12. Сhudyba K. Bezpieczeństwo pożarowe konstrukcji z betonu według eurokodów (norm PN-EN). Bezpieczeństwo i Technika Pożarnicza. 2016; 41(1):85-96. DOI: 10.12845/bitp.41.1.2016.9 (pol).
13. Doherty P., Ali F., Nadjai A., Choi S. Choi Explosive spalling of concrete columns with steel and polypropylene fibres subjected to severe fire. Journal of Structural Fire Engineering. 2012; 3(1):95-104. DOI: 10.1260/2040-2317.3.1.95
14. Siemon M., Zehfuß J. Behavior of structural tunnel elements exposed to fire and mechanical loading. Journal of Structural Fire Engineering. 2018; 9(2):138-146. DOI: 10.1108/JSFE-01-2017-0020
15. Shirsath S.K., Yaragal S.C. Performance of hybrid fibre-reinforced concretes at elevated temperatures. Journal of Structural Fire Engineering. 2017; 8(1):73-83. DOI: 10.1108/JSFE-01-2017-0007
16. Abdi Moghadam Mehrdad, Ramezan Ali Izadifard. Effects of steel and glass fibers on mechanical and durability properties of concrete exposed to high temperatures. Fire Safety Journal. 2020; 113:102978. DOI: 10.1016/j.firesaf.2020.102978
17. Paik J.K., Czujko J. Assessment of hydrocarbon explosion and fire risks in offshore installations: Recent advances and future trends. IES Journal Part A: Civil and Structural Engineering. 2016; 4:167-179. DOI: 10.1080/19373260.2011.593345
18. Shvyrkov S.A., Yuryev Ya.I. The temperature of the fire to determine the limit of fire resistance of enclosing walls of oil tanks. Tekhnologii tekhnosfernoi bezopasnosti: internet-zhurnal. 2016; 4:50-56. URL: http://agps-2006.narod.ru/ttb/2016-4/20-04-16.ttb.pdf (accessed Jule 07, 2021). (rus).
19. Shvyrkov S.A., Petrov A.P., Nazarov V.P., Yuryev Ya.I. Thermophysical characteristic of concrete, shotcrete and fiber-reinforced shotcrete in conditions of hydrocarbon fire. Pozharovzryvobezopasnost /Fire and Explosion Safety. 2016; 25(12):5-12. DOI: 10.18322/PVB.2016.25.12.5-12 (rus).
20. Shvyrkov S.A., Yuryev Ya.I., Pristupyuk D.N. The results of experimental research of strength characteristics of various types of concrete in condition of hydrocarbon fire. Technology of Technosphere Safety. 2017; 1(71). URL: http://agps-2006.narod.ru/ttb/2017-1/16-01-17.ttb.pdf (accessed Jule 07, 2021). (rus).
21. Krutov A.M. Experimental and computational determination of the main parameters of the protective wall for fencing the tank farm of the fuel oil facility at CHPP-11, designed to contain the flow of fuel oil (breakthrough waves) formed during the quasiinstantaneous destruction of the largest reservoir of the group (RVS-20000), as part of the fire protection of the facility located at : Moscow, section of the 4th transport ring, sh. Enthusiasts — Izmailovskoe highway, st. Perovskaya, 1A : research report. Sergiev Posad, ZAO “Teploognezashchita”, 2007; 90. (rus).
22. Roytman V.M. Engineering solutions for assessing the fire resistance of designed and reconstructed buildings. Moscow, Association “Fire Safety and Science”, 2001; 382. (rus).
23. Bubnov V.M., Karpov A.S. Fire resistance of reinforced concrete structures : training manual. Moscow, Academy of the state Fire Service of Emercom of Russia Publ., 2 009; 76. (rus).
Review
For citations:
Shvyrkov S.A., Yuryev Ya.I., Petrov A.P., Nazarov V.P. The analysis of the fire resistance limit of an enclosing wall with a wave-resisting visor as the protection for a group of fuel oil tanks. Pozharovzryvobezopasnost/Fire and Explosion Safety. 2021;30(6):73-86. (In Russ.) https://doi.org/10.22227/0869-7493.2021.30.06.73-86